ANALISIS SHORT CIRCUIT PADA BATERAI FLOODED LEAD ACID (FLA) DAN VALVE REGULATED LEAD ACID (VRLA) DENGAN KAPASITAS 12 V 24 Ah

ZEANDI MARCENDY, NIM.132018013 (2023) ANALISIS SHORT CIRCUIT PADA BATERAI FLOODED LEAD ACID (FLA) DAN VALVE REGULATED LEAD ACID (VRLA) DENGAN KAPASITAS 12 V 24 Ah. Skripsi thesis, Universitas Muhammadiyah Palembang.

[img]
Preview
Text
132018013_BAB_I_DAFTAR_PUSTAKA.pdf

Download (871kB) | Preview
[img] Text
132018013_BAB_II.pdf
Restricted to Repository staff only

Download (760kB)
[img] Text
132018013_BAB_III.pdf
Restricted to Repository staff only

Download (344kB)
[img] Text
132018013_BAB_IV.pdf
Restricted to Repository staff only

Download (608kB)
[img] Text
132018013_BAB_V.pdf
Restricted to Repository staff only

Download (152kB)
[img] Text
132018013_DAFTAR PUSTAKA.pdf
Restricted to Repository staff only

Download (273kB)
[img] Text
132018013_LAMPIRAN.pdf
Restricted to Repository staff only

Download (451kB)
[img] Text
132018013_Cover_Sampai_Lampiran.pdf
Restricted to Repository staff only

Download (1MB)

Abstract

Short circuit on the battery can affect the performance and capacity of the battery, and this can lead to shorter battery life. Short circuits can also cause the battery to overheat and can even cause the battery to be damaged and cannot be used again. The purpose of this research is to determine the difference in the effect of a short circuit on the capacity and performance of FLA and VRLA batteries. Testing the short circuit on the battery using a Dummy load with a resistance of 0.3 ohm 40 Watt with a full charge battery condition. The results showed that the short circuit that occurred in the battery caused the FLA battery voltage to drop by 13% from the initial voltage of 13.53 Vdc, while in the VRLA battery the voltage reduction reaches 14% from the initial voltage of 12.99 Vdc. At the time of short circuit, both FLA and VRLA experienced an increase in current reaching three times the nominal current. From the research results it can be concluded that VRLA batteries have a fairly good endurance compared to FLA batteries after a short circuit occurs. Where VRLA batteries can last 20 minutes longer than FLA batteries, after a short circuit occurs and the battery is connected to the load, with the same total load of 240 watts. Keywords: FLA batteries, VRLA, Short Circuit Battery

Item Type: Thesis (Skripsi)
Additional Information: 1.Wiwin A. Oktaviani, S.T.,M.Sc 2.Taufik Barlian, S.T., M.Eng
Uncontrolled Keywords: FLA batteries, VRLA, Short Circuit Battery
Subjects: Elektro > Pengujian dan Pengukuran Listrik
Elektro > Teknik Listrik
Divisions: Fakultas Teknik > Teknik Elektro (S1)
Depositing User: Mahasiswa Fakultas Teknik
Date Deposited: 18 Jul 2023 04:56
Last Modified: 18 Jul 2023 04:56
URI: http://repository.um-palembang.ac.id/id/eprint/25988

Actions (login required)

View Item View Item

is powered by EPrints 3 which is developed by the School of Electronics and Computer Science at the University of Southampton. More information and software credits.